Address:No.13, West Xiangzhong Road, Xiangyang Industrial Zone, Yueqing City 325619.P.R. China. Zip:325619
ID RESIDUAL CURRENT CIRCUIT BREAKER
Application Residual current circuit breaker provide the function of isolation switching and earth leakage protection of electrical circuits. And also provide the indirect protection of the operators body against the dangerous effects of electric current and provide the protection of the fire caused by the electrical circuit fault.
Technical data Standard:IEC1008,GB16916 Rated Voltage(Un): 2pole:230V AC 4pole:400V AC Rated Current(In):25,40,63A Rated residual operating current(I △n):10、30、100、300、500mA Rated residual non-operation Current( I△no): 0.5I△n Residual current off-time: ≤0.1s Minimum value of rated making and breaking capacity (Im):630A Rated conditional short-circuit current(inc):In=25,40A Inc=1500A In=63A Inc=3000A Endurance: on load:2000 cycles off load:2000 cycles